Contactor Interlock: Keep Two Contactors From Energizing Together

An electrical interlock makes sure two contactors that must never be on together, such as forward and reverse or star and delta, never receive coil voltage at the same time. It is usually built with an NC contact of one contactor in the coil path of the other.

Complements, and does not replace, practice with physical equipment.

Koniami Virtual Lab
Koniami Virtual Lab workspace (illustrative screenshot)
Illustrative workspace screenshot — this module’s own screenshot is coming.

What you practice

  • See where the NC interlock contact sits in the coil path
  • Run the Forward–Reverse and Star–Delta circuits with the interlock in place
  • Remove the interlock and read the behavior findings in the Logic tab
  • Fix the circuit by following the Guide

Wiring mistakes it can recognize

  • Interlock only in the seal-in branch

    It does not protect at start, so both contactors can still be on together.

  • Interlock taken from the wrong contactor

    The contact does not represent the opposing contactor, so the protection does not work.

  • No interlock at all

    When both are on, the phases short-circuit; the Logic diagnostics show the path.